MG WIRES / KARTA KATALOGOWA
ZAPYTAJ O OFERTĘ →
PL
H00S-D
H00S-D single-core cable for grounding and short-circuiting equipment.

01
Key parameters
- Operating temperature according to standard
- −40 °C to +70 °C
- Minimum bending radius
- 4 × cable diameter
- AC test voltage
- 10–16 kV depending on wall thickness
- DC test voltage
- 15–22 kV depending on wall thickness
02
Construction
- Conductor
- Soft bare copper, class 6 according to EN 60228
- Insulation
- SiR silicone rubber
- Insulation color
- Transparent
- Insulation material temperature range
- −60 °C to +200 °C
- Insulation material short-term temperature
- +230 °C
03
Properties
Resistance to thermal shock, UV radiation and aging. Mechanical strength and flexibility. Permanent marking printed under the insulation.
04
Standards
PN-EN 61138:2009; EN 60228, class 6.
05
Technical tables
Dimensions — H00S-D
| Nominal core cross-section [mm²] | Largest wire diameter in strand [mm] | Nominal insulation thickness [mm] | Approximate outside cable diameter [mm] | Approximate cable weight [kg/km] |
|---|---|---|---|---|
| 16 | 0,21 | 1,4 | 8,4 ± 0,2 | 184 |
| 25 | 0,21 | 1,4 | 10,4 ± 0,2 | 300 |
| 35 | 0,21 | 1,4 | 11,4 ± 0,2 | 404 |
| 50 | 0,31 | 1,6 | 13,4 ± 0,2 | 570 |
| 70 | 0,31 | 2,1 | 16,4 ± 0,2 | 820 |
| 95 | 0,31 | 2,3 | 19,3 ± 0,2 | 1104 |
| 120 | 0,31 | 2,7 | 21,6 ± 0,2 | 1430 |
06
Available versions
Cable reels or drums.