Key parameters

Continuous working temperature
−40 °C to +90 °C
Elevated working temperature
Maximum +120 °C for 20 000 h
DC operating voltage
1.5 kV, maximum 1.8 kV
AC rated voltage
1.0/1.0 kV
Maximum conductor temperature in operation
+90 °C
Short-circuit temperature
+250 °C, maximum 5 s on conductor
Minimum allowable ambient temperature
−40 °C
Minimum installation temperature
−25 °C
Test voltage, 50 Hz
6500 V AC
Minimum bending radius
4 × cable diameter
Expected period of use
25 years
CPR reaction-to-fire class
B2ca s2, d2, a3 according to EN 50575
EN 50618 test certificate
1260012

Electrical Specifications

Max permissible operating voltage
1,2/1,2 kVAC 1,8/1,8 kVDC (conductor-conductor, conductor-ground)H1Z2Z2-K B2ca, 4–25 mm²
Resistance of the conductor
EN 50395, clause 5 acc. EN 50618, table 2H1Z2Z2-K B2ca, 4–25 mm²
Voltage test on cable with AC or DC
EN 50395, clause 5 (6,5 kVAC or 15 kVDC, 5 min)H1Z2Z2-K B2ca, 4–25 mm²
Surface resistance
EN 50395, clause 11H1Z2Z2-K B2ca, 4–25 mm²

Thermal Specifications

Cold bending test
EN 60811-504 (-40 °C, duration of conditioning: 16 h)H1Z2Z2-K B2ca, 4–25 mm²

Specifications regarding safety

Resistance against acid and alkaline solution
EN 60811-404 7 days; 23 °C (N-Oxalic-acid; N-Sodium hydroxide solution)H1Z2Z2-K B2ca, 4–25 mm²
Ozone resistance on completed cable
EN 50396 clause 8.1.3, method BH1Z2Z2-K B2ca, 4–25 mm²
Weathering/ UV-resistance on sheath
meets EN 50618, Annex E EN 50289-4-17, method A (720 h; 60 °C ± 3 °C; 50 ± 5 % relative humidity)H1Z2Z2-K B2ca, 4–25 mm²
02

Construction

Conductor
Soft-annealed tin-plated electrolytic copper Cu-ETP1, class 5 according to IEC 60228 and DIN EN 13602
Insulation
Crosslinked special halogen-free compound, white
Outer sheath
Crosslinked special halogen-free compound, black, red or blue

Electrical Specifications

Insulation resistance
EN 50395 clause 8.1 performed at 20 °C & 90 °C in water results acc. to EN 50618, table 1H1Z2Z2-K B2ca, 4–25 mm²
03

Properties

UV and weathering resistance according to EN 50618. Resistance to ammonia. Halogen-free, resistant to acids and alkalis.

Additional tests

AD8 water resistance and direct burial tests according to UL 854, sections 23 and 24.

04

Standards

PN-EN 50618:2015-03; EN 60332-1; IEC 60332-1; PN-EN 61034-2; PN-EN 60754-2; EN 50575; IEC 60228; DIN EN 13602.

05

Application

Connections between individual solar panels and between panels and the inverter in photovoltaic installations.

06

Technical tables

Dimensions

Dimensions
Cross-section [mm²]Maximum diameter of single wire in conductor [mm]Nominal insulation thickness [mm]Nominal jacket thickness [mm]Maximum outside cable diameter [mm]Minimum insulation resistance at 20 °C [MΩ·km]Minimum insulation resistance at 90 °C [MΩ·km]
40,310,70,86,65800,58
60,310,70,87,45000,50
100,410,70,88,84200,42
160,410,70,910,13400,34
250,410,91,012,53400,34

Other cross-sections and constructions are available on request.

Current carrying capacity

Current carrying capacity
Cross-section [mm²]Single cable free in air [A]Single cable on a surface [A]Two loaded cables touching on a surface [A]
4555244
6706757
10989379
16132125107
25176167142
07

Available versions

Black, red or blue outer sheath. Optional galvanized steel wire FeZn reinforcement. Other cross-sections and constructions are available on request.

08

Additional information

Electrical Specifications

Spark test
EN 62230, Annex AH1Z2Z2-K B2ca, 4–25 mm²

Mechanical Specifications

Properties before ageing
EN 60811-1-1; EN 60811-1-2 (tensile strength insulation ≥ 8,0 N/mm² tensile strength jacket ≥ 8,0 N/mm² elongation at break ≥ 125 %)H1Z2Z2-K B2ca, 4–25 mm²
Hot Set test
EN 60811-2-1 (250 °C; 15 min. under load; 20 N/cm² stress)H1Z2Z2-K B2ca, 4–25 mm²
Dynamic penetration test
acc. to EN 50618 - Annex DH1Z2Z2-K B2ca, 4–25 mm²

Thermal Specifications

Damp heat test
EN 60068-2-78 (1.000 h at 90 °C and 85 % relative humidity)H1Z2Z2-K B2ca, 4–25 mm²
Shrinkage test
EN 60811-503 (120 °C, 1 h, shrinkage <2,0%)H1Z2Z2-K B2ca, 4–25 mm²
Cold elongation test
EN 60811-505 (-40 °C ± 2 °C, duration of conditioning: 16 h)H1Z2Z2-K B2ca, 4–25 mm²
Cold impact test
EN 60811-506 and EN 50618, Annex C (-40 °C; mass of hammer 1.000 g)H1Z2Z2-K B2ca, 4–25 mm²

Specifications regarding safety

Construction Product Regulation (CPR)
class B2ca s2, d2, a3 in accordance with EN 50575:2014 ITB certificate-No 1488-CPR-1038/WH1Z2Z2-K B2ca, 4–25 mm²
Test for vertical flame propagation on complete cable
EN 60332-1-2H1Z2Z2-K B2ca, 4–25 mm²

Additional external tests

Direct burial
External tests in UL Laboratory in USA acc. To UL 854: -Section 23 Impact-resistance Test -Section 24 Crushing-Resistance TestH1Z2Z2-K B2ca, 4–25 mm²
Classification to the category AD8
External tests in EZU Laboratory in Praha tested acc. to EN 50525-21 – Annex E: - Voltage at 1 kV on cable in water at 50 °C during 10 days without any break - Water absorption on sheath after immersion 10 days at 50 °C less than 40 % - Insulation resistance tests with a minimum resistivity of 10¹¹ Ω·cmH1Z2Z2-K B2ca, 4–25 mm²
Certificates & Guidelines
EN 50618: EZU certificate-Nr. 1260012 EN 50575, EN 50575:2014/A12016: ITB certificate-Nr. 1488-CPR-1038/W RoHS 2011/65/EU +2015/863/EU REACH 1907/2006H1Z2Z2-K B2ca, 4–25 mm²