H1Z2Z2-K B2ca

H1Z2Z2-K B2ca cable with halogen-free insulation and jacket, for photovoltaic systems.

REQUEST A QUOTE → EN
Ilustracja H1Z2Z2-K B2ca.
Illustration H1Z2Z2-K B2ca.
01

Key Parameters

Operating temperature
−40 °C to +90 °C
Elevated operating temperature
Up to +120 °C for 20,000 hours
DC Operating Voltage
1.5 kV, up to 1.8 kV
Rated AC voltage
1.0/1.0 kV
Maximum core temperature during operation
+90 °C
Short-circuit temperature
+250 °C, for a maximum of 5 seconds on the wire
Minimum ambient temperature for permanent installation
−40 °C
Minimum installation temperature
−25 °C
Test voltage: 50 Hz
6,500 V AC
Minimum bending radius for permanent installation
4 × cable diameter
Expected service life
25 years
CPR Fire Reaction Class
B2ca s2, d2, a3 according to EN 50575
EN 50618 Certificate
1260012

Electrical Requirements

Maximum Allowable Operating Voltage
1.2/1.2 kVAC, 1.8/1.8 kVDC (wire-to-wire, wire-to-ground)H1Z2Z2-K B2ca, range 4–25 mm²
Cable resistance
EN 50395, Section 5 according to EN 50618, Table 2H1Z2Z2-K B2ca, range 4–25 mm²
AC/DC Voltage Test on a Cable
EN 50395, Section 5 (6.5 kVAC or 15 kVDC, 5 minutes)H1Z2Z2-K B2ca, range 4–25 mm²
Surface resistance
EN 50395, Section 11H1Z2Z2-K B2ca, range 4–25 mm²
Insulation Resistance
EN 50395, Section 8.1: The tests were conducted at temperatures of 20 °C and 90 °C in water; results according to EN 50618, Table 1H1Z2Z2-K B2ca, range 4–25 mm²
Tensile Test on a Sliding Specimen
EN 62230, Annex AH1Z2Z2-K B2ca, range 4–25 mm²

Thermal Requirements

Testing at elevated temperature and humidity
EN 60068-2-78 (1,000 hours at 90 °C and 85% relative humidity)H1Z2Z2-K B2ca, range 4–25 mm²
Low-Temperature Winding Test
EN 60811-504 (–40 °C, acclimatization: 16 hours)H1Z2Z2-K B2ca, range 4–25 mm²
Low-Temperature Expansion Test
EN 60811-505 (–40 ±2 °C, acclimatization: 16 hours)H1Z2Z2-K B2ca, range 4–25 mm²
Low-Temperature Impact Resistance Test
EN 60811-506 and EN 50618, Annex C (–40 °C; hammer mass 1000 g)H1Z2Z2-K B2ca, range 4–25 mm²
02

Construction

Vein
Tin-plated electrolytic copper Cu-ETP1, Class 5 according to IEC 60228 and DIN EN 13602
Insulation
Special halogen-free cross-linked plastic, white
Coating
Special halogen-free cross-linked plastic, available in black, red, or blue
03

Properties

Mechanical Requirements

Anti-aging properties
EN 60811-1-1; EN 60811-1-2 (Insulation tensile strength ≥ 8.0 N/mm²; outer insulation tensile strength ≥ 8.0 N/mm²; elongation at break ≥ 125%)H1Z2Z2-K B2ca, range 4–25 mm²
Thermal Expansion Test
EN 60811-2-1 (250 °C; 15 min under load; load of 20 N/cm²)H1Z2Z2-K B2ca, range 4–25 mm²
Dynamic Permeation Test
According to EN 50618, Annex DH1Z2Z2-K B2ca, range 4–25 mm²

Thermal Requirements

Contraction Test
EN 60811-503 (120 °C, 1 hour, shrinkage <2.0%)H1Z2Z2-K B2ca, range 4–25 mm²

Safety Requirements

Resistance to acids and alkalis
EN 60811-404 7 days; 23 °C (oxalic acid N; sodium hydroxide solution N)H1Z2Z2-K B2ca, range 4–25 mm²
Testing the Resistance of a Complete Cable to Ozone Exposure
EN 50396, Section 8.1.3, Procedure BH1Z2Z2-K B2ca, range 4–25 mm²
Weathering / UV testing of exterior insulation
Complies with EN 50618, Annex E of EN 50289-4-17, Procedure A (720 h; 60 °C ± 3 °C; relative humidity 50 ± 5%)H1Z2Z2-K B2ca, range 4–25 mm²
Test of Vertical Flame Spread on a Complete Cable
EN 60332-1-2H1Z2Z2-K B2ca, range 4–25 mm²

Additional external studies

Can be installed underground
Testing at an accredited UL laboratory in the U.S. in accordance with UL 854: - Section 23: Impact Resistance Test - Section 24: Crushing Resistance TestH1Z2Z2-K B2ca, range 4–25 mm²
Classification in Category AD8
Testing conducted at the accredited EZU laboratory in Prague in accordance with EN 50525-21—Annex E—included the following: - a voltage test in water at 1 kV AC, at a temperature of 50 °C for 10 consecutive days - water absorption through the outer insulation after 10 days of storage in water at 50 °C <40% - insulation resistance: min. 10¹¹ Ω·cmH1Z2Z2-K B2ca, range 4–25 mm²
Directives and Certificates
EN 50618: EZU Certificate No. 1260012 EN 50575, EN 50575:2014/A12016: ITB Certificate No. 1488-CPR-1038/W RoHS 2011/65/EU + 2015/863/EU REACH 1907/2006H1Z2Z2-K B2ca, range 4–25 mm²

Resistant to UV, ozone, hydrolysis, and ammonia. Halogen-free construction with enhanced resistance to acids and bases.

04

Standards

PN-EN 50618:2015-03; EN 60332-1; IEC 60332-1; PN-EN 61034-2; PN-EN 60754-2; EN 50575; IEC 60228; DIN EN 13602.

05

Application

Connections between solar panels and between the panels and the inverter.

06

Technical Tables

Dimensions

Dimensions
Wire cross-sectional area [mm²]Maximum wire diameter in a strand [mm]Nominal insulation thickness [mm]Nominal coating thickness [mm]Maximum cable diameter [mm]Minimum insulation resistance at 20 °C [MΩ·km]Minimum insulation resistance at 90 °C [MΩ·km]
40,310,70,86,65800,58
60,310,70,87,45000,50
100,410,70,88,84200,42
160,410,70,910,13400,34
250,410,91,012,53400,34

Other cross-sections and designs are available upon request.

Current-Carrying Capacity

Current-Carrying Capacity
Wire cross-sectional area [mm²]A single overhead cable [A]A single cable on the surface [A]Two cables side by side on surface [A]
4555244
6706757
10989379
16132125107
25176167142
07

Available versions

Available in black, red, or blue. Can be manufactured with FeZn-galvanized steel wire reinforcement. Other cross-sections and designs available upon request. A rodent-repellent additive can be added.

08

Additional information

Additional Tests

Enhanced water resistance (AD8); suitability for direct installation in the ground confirmed by UL 854 testing, sections 23 and 24.

09