N2XH-J
N2XH-J halogen-free power and control cable with a rated voltage of 0.6/1 kV.

Key Parameters
- Rated voltage
- 0.6/1.0 kV
- Maximum core temperature during operation
- +90 °C
- Short-circuit temperature
- +250 °C, for a maximum of 5 seconds on the wire
- Minimum ambient temperature for permanent installation
- −30 °C
- Installation temperature
- −5 °C to +50 °C
- Test voltage, 50 Hz
- 4,000 V AC
- Minimum bending radius
- Single-conductor cables: 15 × cable diameter; multi-conductor cables: 12 × cable diameter
Construction
- Vein
- Bare copper Cu-ETP1, Class 1 or 2 according to IEC 60228 and DIN EN 13602
- Insulation
- Halogen-free cross-linked polyethylene (XLPE), HD 604 S1, Type 2XI1
- Multi-conductor cable terminations
- Twisted wires with optimal pitch
- Filling
- Self-extinguishing, halogen-free thermoplastic compound
- Coating
- Halogen-free HM4 plastic in accordance with HD 604 S1, black
- Wire Markings
- In accordance with DIN VDE 0293-308; equipped with a yellow-green protective conductor
Properties
Halogen-free cable with enhanced fire resistance.
Standards
DIN VDE 0276-604; HD 604 S1-1+5G; IEC 60228; DIN EN 13602; DIN VDE 0293-308; PN-EN 60332-1; EN 60332-1; IEC 60332-1; PN-EN 60754-2; EN 60754-2; IEC 60754-1; IEC 60754-2; PN-EN 50575.
Application
Permanent installations in facilities requiring protection of people and property in the event of a fire, including hotels, hospitals, schools, airports, subways, railways, and industrial facilities. Installation in dry and damp environments: on plaster, under plaster, flush with plaster, in masonry walls, and directly in concrete. Cable ducts or protective conduits are required for outdoor or underground installation.
Technical Tables
Dimensions of single-conductor cables
| Number and cross-sectional area of conductors [mm²] | Cable diameter [mm] | Cable weight [kg/km] |
|---|---|---|
| 1 x 1,5 RE | 5,2 | 39 |
| 1 x 2,5 RE | 5,5 | 51 |
| 1 x 4 RE | 6,0 | 67 |
| 1 x 6 RE | 6,5 | 87 |
| 1 x 10 RM | 7,3 | 128 |
| 1 x 16 RM | 8,3 | 194 |
| 1 x 25 RM | 10,2 | 292 |
| 1 x 35 RM | 11,4 | 386 |
RE — single-strand round conductors; RM — multi-strand round conductors.
Dimensions of Multi-Conductor Cables
| Number and cross-sectional area of conductors [mm²] | Cable diameter [mm] | Cable weight [kg/km] |
|---|---|---|
| 2 x 1,5 RE | 8,9 | 119 |
| 2 x 2,5 RE | 9,7 | 150 |
| 2 x 4 RE | 10,6 | 195 |
| 2 x 6 RE | 11,6 | 250 |
| 2 x 10 RM | 13,2 | 360 |
| 2 x 16 RM | 15,5 | 542 |
| 3 x 1,5 RE | 9,3 | 134 |
| 3 x 2,5 RE | 10,1 | 174 |
| 3 x 4 RE | 11,1 | 231 |
| 3 x 6 RE | 12,2 | 302 |
| 3 x 10 RM | 14,2 | 454 |
| 3 x 16 RM | 16,4 | 683 |
| 4 x 1,5 RE | 10,0 | 157 |
| 4 x 2,5 RE | 10,9 | 207 |
| 4 x 4 RE | 12,1 | 278 |
| 4 x 6 RE | 13,3 | 372 |
| 4x 10 RM | 15,5 | 564 |
| 4 x 16 RM | 18,0 | 858 |
| 5 x 1,5 RE | 10,8 | 184 |
| 5 x 2,5 RE | 11,9 | 245 |
| 5 x 4 RE | 13,1 | 333 |
| 5 x 6 RE | 14,7 | 455 |
| 5 x 10 RM | 17,0 | 682 |
| 7 x 1,5 RE | 11,9 | 231 |
| 7 x 2,5 RE | 13,0 | 311 |
| 7 x 4 RE | 14,9 | 447 |
RE — single-strand round conductors; RM — multi-strand round conductors.