H07V-K (LgY)

Part Number: H07V-K

Also known as: LgY

REQUEST A QUOTE →
Barwa i przekrój zależą od wykonania.
The color and cross-section depend on the model.
01

Key Parameters

Constant operating temperature
-30 °C to +70 °C
Rated voltage
450/750 V
Maximum conductor temperature during cable operation
+70 °C
Minimum ambient temperature for permanently installed cables
-30 °C
Minimum cable installation temperature
-5 °C
Test voltage at 50 Hz
3,500 V (AC)
Minimum bending radius for permanent joints
12.5 x Ø

H07V-K UV — 120 mm²

Constant operating temperature
-25 °C to +70 °C.
02

Construction

A wire made of bare or tinned electrolytic copper (Cu-ETP1, Class 5) in accordance with the standard
IEC/EN 60228.
Insulation
Insulating PVC, color: as specified in the order.

The cable is marked with the manufacturer's name, the cable type and cross-section, and the production lot number.

H07V-K UV — 120 mm²

Vein
Class 5 flexible cable made of bare Cu-ETP1 copper in accordance with EN 60228.
Insulation
PVC T1 material compliant with the EN 50363-3 standard,

Available in all colors, including two-tone options.

03

Properties

The cable complies with the requirements of the Low-Voltage Directive 2014/35/EU

H07V-K UV — 120 mm²

Good moisture resistance.
Good mechanical strength.

04

Standards

PN-EN 50525-2-31

H07V-K UV — 120 mm²

PN-EN 50525-2-31

05

Application

H07V-K UV — 120 mm²

General-purpose power cables.

06

Technical Tables

Technical Specifications — H07V-K

Technical Specifications — H07V-K
Number of conductors × conductor cross-sectional area [mm²]Outer diameter approximately [mm]Copper Index [kg/km]Cable weight [kg/km]
1 X 1,502,9014,419,0
1 X 2,53,5024,029,0
1 X 44,0038,443,0
1 X 64,6057,661
1 X 106,1096,0120,0
1 X 167,20154,0181,0
1 X 258,90240,0274,0
1 X 3510,1336,0380,0
1 X 5012,4480,0545,0
1 X 7013,5665,0790,0

H07V-K UV — 120 mm²

Technical Specifications — H07V-K UV — 120 mm²
Conductor cross-sectional area [mm²]Max. wire diameter in a strand [mm]Nominal insulation thickness [mm]Min. outer diameter of the cable [mm]Max. outer diameter of the cable [mm]
1200,511,6016,7020,20

Other cross-sections and designs are available upon request.