Skip to main content

MGWIRES

PRODUCT CATALOG Find a specific cable
MG WIRES / TECHNICAL DATA

H1Z2Z2-K US

H1Z2Z2-K US cable for photovoltaic installations, with halogen-free insulation and jacket, and an outer armor made of galvanized steel wires.

REQUEST A QUOTE →
Ilustracja wykonania US z oplotem stalowym FeZn.
Illustration of a US with FeZn steel braiding.
01

Key Parameters

Operating temperature
−40 °C to +90 °C
Elevated operating temperature
Up to +120 °C for 20,000 hours
DC Operating Voltage
1.5 kV, up to 1.8 kV
Rated AC voltage
1.0/1.0 kV
Maximum core temperature during operation
+90 °C
Short-circuit temperature
+250 °C, for a maximum of 5 seconds on the wire
Minimum ambient temperature for permanent installation
−40 °C
Minimum installation temperature
−25 °C
Test voltage: 50 Hz
6,500 V AC
Minimum bending radius for permanent installation
4 × cable diameter
Expected service life
25 years
CPR Fire Reaction Class
Dca according to EN 50575
EN 50618 Certificate
1250124
02

Construction

Vein
Tin-plated electrolytic copper Cu-ETP1, Class 5 according to IEC 60228 and DIN EN 13602
Insulation
Special halogen-free cross-linked plastic, white
Coating
Special halogen-free cross-linked plastic, available in black, red, or blue
Armament
Outer braid made of FeZn-galvanized steel wires; minimum braid density of 90%
03

Properties

Resistant to UV, ozone, hydrolysis, and ammonia. Halogen-free construction with enhanced resistance to acids and bases.

04

Standards

PN-EN 50618:2015-03; EN 60332-1; IEC 60332-1; PN-EN 61034-2; PN-EN 60754-2; EN 50575; IEC 60228; DIN EN 13602.

05

Application

Connections between solar panels and between the panels and the inverter. The FeZn external coating enhances resistance to mechanical damage and damage caused by rodents.

06

Technical Tables

US production

Dimensions and Insulation — US Version
Wire cross-sectional area [mm²]Maximum wire diameter in a strand [mm]Nominal insulation thickness [mm]Nominal coating thickness [mm]Approximate diameter of the cable in the conduit [mm]Minimum insulation resistance at 20 °C [MΩ·km]Minimum insulation resistance at 90 °C [MΩ·km]
2,50,260,70,85,16900,86
40,310,70,86,05800,58
60,310,70,86,75000,50
100,410,70,88,54200,42
160,410,70,99,43400,34
250,410,91,012,03400,34

Other cross-sections and designs are available upon request.

Current-Carrying Capacity

Current-Carrying Capacity
Wire cross-sectional area [mm²]A single overhead cable [A]A single cable on the surface [A]Two cables side by side on surface [A]
2,5413933
4555244
6706757
10989379
16132125107
25176167142
07

Available versions

Black, red, or blue coating. Other cross-sections and designs are available upon request.

08

Documentation