Skip to main content

MGWIRES

PRODUCT CATALOG Find a specific cable
MG WIRES / TECHNICAL DATA

H00V-D

H00V-D single-conductor cable designed for grounding and bonding equipment.

REQUEST A QUOTE → EN
H00V-D — ilustracja poglądowa zaakceptowana przez MG Wires
Illustration for illustrative purposes only.
01

Key Parameters

Operating temperature of the cable according to the standard
−5 °C to +70 °C
Minimum bending radius
4 × cable diameter
AC Test Voltage
10–16 kV, depending on the wall thickness
DC test voltage
15–22 kV, depending on the wall thickness
Temperature range of the insulation material
−25 °C to +70 °C
Short-term temperature of the insulation material
+100 °C
02

Construction

Vein
Bare soft copper, Grade 6
Insulation
Polyvinyl chloride (PVC)/ST5
Insulation Color
Transparent
03

Properties

Resistance to thermal shock, UV radiation, and aging. High flexibility and mechanical strength. Permanent marking in the form of a print under the insulation.

04

Standards

PN-EN 61138:2009; EN 60228, Class 6.

05

Technical Tables

H00V-D / H00V3-D

Dimensions — H00V-D / H00V3-D
Rated conductor cross-sectional area [mm²]Maximum wire diameter in the strand [mm]Rated insulation thickness [mm]Approximate cable diameter [mm]Approximate cable weight [kg/km]
160,211,28,0 ± 0,2196
250,211,210,0 ± 0,2312
350,211,211,0 ± 0,2417
500,311,513,2 ± 0,2610
700,311,815,8 ± 0,2930
950,311,818,3 ± 0,21234
1200,311,819,9 ± 0,21570
06

Available versions

Cable reels or drums.