MG WIRES / TECHNICAL DATA
REQUEST A QUOTE →
H07V2-K (LgYc)
Part Number: H07V2-K
Also known as: LgYc
Low-voltage, single-conductor, general-purpose power cables, unsheathed, with thermoplastic polyvinyl chloride (PVC) insulation. H07V2-K – cable manufactured in accordance with a harmonized standard (H), rated for 450/750 V (07), with heat-resistant polyvinyl chloride (PVC) insulation (V2), featuring a flexible multi-strand conductor (K)
01
Key Parameters
- Operating temperature of cables
- up to +90 °C
02
Construction
- Vein
- Copper, multi-strand, flexible, Class 5 (per EN 60228)
- Insulation
- PVC – TI 3, compliant with EN 50363-3
03
Standards
STANDARD: PN-EN 50525-2-31
04
Technical Tables
| Nominal cross-sectional area / mm² | Diameter of a single wire / (max.) / mm | Resistance at 20 °C / (max.) / mΩ/m | Insulation wall thickness / (nom.) / mm | Outer diameter of the cable / (min.) / mm | Outer diameter of the cable / (max.) / mm |
|---|---|---|---|---|---|
| 1,50 | 0,26 | 13,3 | 0,7 | 2,8 | 3,4 |
| 2,50 | 0,26 | 7,98 | 0,8 | 3,4 | 4,1 |
| 4,00 | 0,31 | 4,95 | 0,8 | 3,9 | 4,8 |
| 6,00 | 0,31 | 3,30 | 0,8 | 4,4 | 5,3 |
| 10,00 | 0,41 | 1,91 | 1,0 | 5,7 | 6,8 |
| 16,00 | 0,41 | 1,21 | 1,0 | 6,7 | 8,1 |
| 25,00 | 0,41 | 0,78 | 1,2 | 8,4 | 10,2 |
| 35,00 | 0,41 | 0,554 | 1,2 | 9,7 | 11,7 |
| 50,00 | 0,41 | 0,386 | 1,4 | 11,5 | 13,9 |
| 70,00 | 0,51 | 0,272 | 1,4 | 13,2 | 16,0 |
| 95,00 | 0,51 | 0,206 | 1,6 | 15,1 | 18,2 |
| 120,00 | 0,51 | 0,161 | 1,6 | 16,7 | 20,2 |