MG WIRES / TECHNICAL DATA
REQUEST A QUOTE →
EN
H00V3-D
H00V3-D single-conductor cable designed for grounding and bonding equipment.

01
Key Parameters
- Operating temperature of the cable according to the standard
- −25 °C to +55 °C
- Minimum bending radius
- 4 × cable diameter
- AC Test Voltage
- 10–16 kV, depending on the wall thickness
- DC test voltage
- 15–22 kV, depending on the wall thickness
- Temperature range of the insulation material
- −40 °C to +60 °C
- Short-term temperature of the insulation material
- +90 °C
02
Construction
- Vein
- Bare soft copper, Grade 6
- Insulation
- Freeze-resistant polyvinyl chloride (PVC/ST11)
- Insulation Color
- Transparent
03
Properties
Resistance to thermal shock, UV radiation, and aging. High flexibility and mechanical strength. Permanent marking in the form of a print under the insulation.
04
Standards
PN-EN 61138:2009; EN 60228, Class 6.
05
Technical Tables
H00V-D / H00V3-D
| Rated conductor cross-sectional area [mm²] | Maximum wire diameter in the strand [mm] | Rated insulation thickness [mm] | Approximate cable diameter [mm] | Approximate cable weight [kg/km] |
|---|---|---|---|---|
| 16 | 0,21 | 1,2 | 8,0 ± 0,2 | 196 |
| 25 | 0,21 | 1,2 | 10,0 ± 0,2 | 312 |
| 35 | 0,21 | 1,2 | 11,0 ± 0,2 | 417 |
| 50 | 0,31 | 1,5 | 13,2 ± 0,2 | 610 |
| 70 | 0,31 | 1,8 | 15,8 ± 0,2 | 930 |
| 95 | 0,31 | 1,8 | 18,3 ± 0,2 | 1234 |
| 120 | 0,31 | 1,8 | 19,9 ± 0,2 | 1570 |
06
Available versions
Cable reels or drums.