MG WIRES / TECHNICAL DATA
REQUEST A QUOTE →
EN
H00S-D
H00S-D single-conductor cable designed for grounding and bonding equipment.

01
Key Parameters
- Operating temperature of the cable according to the standard
- −40 °C to +70 °C
- Minimum bending radius
- 4 × cable diameter
- AC Test Voltage
- 10–16 kV, depending on the wall thickness
- DC test voltage
- 15–22 kV, depending on the wall thickness
- Temperature range of the insulation material
- −60 °C to +200 °C
- Short-term temperature of the insulation material
- +230 °C
02
Construction
- Vein
- Bare soft copper, Grade 6
- Insulation
- SiR Silicone Rubber
- Insulation Color
- Transparent
03
Properties
Resistance to thermal shock, UV radiation, and aging. High flexibility and mechanical strength. Permanent marking in the form of a print under the insulation.
04
Standards
PN-EN 61138:2009; EN 60228, Class 6.
05
Technical Tables
Dimensions — H00S-D
| Rated conductor cross-sectional area [mm²] | Maximum wire diameter in the strand [mm] | Rated insulation thickness [mm] | Approximate cable diameter [mm] | Approximate cable weight [kg/km] |
|---|---|---|---|---|
| 16 | 0,21 | 1,4 | 8,4 ± 0,2 | 184 |
| 25 | 0,21 | 1,4 | 10,4 ± 0,2 | 300 |
| 35 | 0,21 | 1,4 | 11,4 ± 0,2 | 404 |
| 50 | 0,31 | 1,6 | 13,4 ± 0,2 | 570 |
| 70 | 0,31 | 2,1 | 16,4 ± 0,2 | 820 |
| 95 | 0,31 | 2,3 | 19,3 ± 0,2 | 1104 |
| 120 | 0,31 | 2,7 | 21,6 ± 0,2 | 1430 |
06
Available versions
Cable reels or drums.
07