01
Key Parameters
- Constant operating temperature
- -40 °C to +90 °C.
- Operating voltage
- 450/750 V
02
Construction
- Vein
- Class 5 flexible cable made of bare Cu-ETP1 copper in accordance with EN 60228.
- Insulation
- halogen-free EI5-rated plastic compliant with EN 50363-5,
Available in all colors, including two-tone options.
03
Properties
Good moisture resistance and enhanced UV resistance.
Good mechanical strength.
04
Standards
PN-EN 50525-3-41
05
Technical Tables
Technical Specifications — H07Z-K
| Conductor cross-sectional area [mm²] | Max. wire diameter in a strand [mm] | Nominal insulation thickness [mm] | Min. outer diameter of the cable [mm] | Max. outer diameter of the cable [mm] |
|---|---|---|---|---|
| 1,5 | 0,26 | 0,7 | 2,8 | 3,5 |
| 2,5 | 0,26 | 0,8 | 3,4 | 4,3 |
| 4 | 0,31 | 0,8 | 3,9 | 4,9 |
| 6 | 0,31 | 0,8 | 4,4 | 5,5 |
| 10 | 0,41 | 1,0 | 5,7 | 7,1 |
| 16 | 0,41 | 1,0 | 6,7 | 8,4 |
| 25 | 0,41 | 1,2 | 8,4 | 10,6 |
| 35 | 0,41 | 1,2 | 9,7 | 12,1 |
| 50 | 0,41 | 1,4 | 11,5 | 14,4 |
| 70 | 0,51 | 1,4 | 13,2 | 16,6 |
| 95 | 0,51 | 1,6 | 16,7 | 20,9 |
06