MG WIRES / TECHNICAL DATA
REQUEST A QUOTE →
H05V2V2-F
Low-voltage multi-conductor power cables rated for a voltage not exceeding 300/500 V. General-purpose cables with thermoplastic polyvinyl chloride (PVC) insulation.
01
Key Parameters
- Operating temperature of cables
- up to +90 °C
02
Construction
- Vein
- Copper, multi-strand, flexible, Class 5 (per EN 60228)
- Insulation
- PVC, Type TI3 (according to EN 50363-3)
- Coating
- PVC, Type TM3 (according to EN 50363-4-1)
03
Standards
STANDARD: PN-EN 50525-2-11
04
Technical Tables
Round Performance Table
| Number of conductors × Nominal cross-sectional area / mm² | Diameter of a single wire / (max.) / mm | Resistance at 20 °C / (max.) / mΩ/m | Insulation wall thickness / (nom.) / mm | Coating wall thickness / (nom.) / mm | Outer diameter of the cable / (min.) / mm | Outer diameter of the cable / (max.) / mm |
|---|---|---|---|---|---|---|
| 2 x 0,75 | 0,21 | 26,0 | 0,6 | 0,8 | 5,7 | 7,2 |
| 2 x 1 | 0,21 | 19,5 | 0,6 | 0,8 | 5,9 | 7,5 |
| 2 x 1,5 | 0,26 | 13,3 | 0,7 | 0,8 | 6,8 | 8,6 |
| 2 x 2,5 | 0,26 | 7,98 | 0,8 | 1,0 | 8,4 | 10,6 |
| 2 x 4 | 0,31 | 4,95 | 0,8 | 1,1 | 9,7 | 12,1 |
| 3 x 0,75 | 0,21 | 26,0 | 0,6 | 0,8 | 6,0 | 7,6 |
| 3 x 1 | 0,21 | 19,5 | 0,6 | 0,8 | 6,3 | 8,0 |
| 3 x 1,5 | 0,26 | 13,3 | 0,7 | 0,9 | 7,4 | 9,4 |
| 3 x 2,5 | 0,26 | 7,98 | 0,8 | 1,1 | 9,2 | 11,4 |
| 3 x 4 | 0,31 | 4,95 | 0,8 | 1,2 | 10,5 | 13,1 |
| 4 x 0,75 | 0,21 | 26,0 | 0,6 | 0,8 | 6,6 | 8,3 |
| 4 x 1 | 0,21 | 19,5 | 0,6 | 0,9 | 7,1 | 9,0 |
| 4 x 1,5 | 0,26 | 13,3 | 0,7 | 1,0 | 8,4 | 10,5 |
| 4 x 2,5 | 0,26 | 7,98 | 0,8 | 1,1 | 10,1 | 12,5 |
| 4 x 4 | 0,31 | 4,95 | 0,8 | 1,2 | 11,5 | 14,3 |
| 5 x 0,75 | 0,21 | 26,0 | 0,6 | 0,9 | 7,4 | 9,3 |
| 5 x 1 | 0,21 | 19,5 | 0,6 | 0,9 | 7,8 | 9,8 |
| 5 x 1,5 | 0,26 | 13,3 | 0,7 | 1,1 | 9,3 | 11,6 |
| 5 x 2,5 | 0,26 | 7,98 | 0,8 | 1,2 | 11,2 | 13,9 |
| 5 x 4 | 0,31 | 4,95 | 0,8 | 1,4 | 13,0 | 16,1 |
Excluding H2 flat varieties.