MG WIRES / TECHNICAL DATA

(N)HXAF 0.6/1 kV

Halogen-free power cables are used for permanent and safe installations. This product series is recommended for use in confined spaces where an optimal bending radius is required. These cables are designed to withstand harsh operating conditions (oil, ozone, temperature fluctuations, etc.).

REQUEST A QUOTE →
Ilustracja (N)HXAF.
(N)HXAF illustration.
01

Key Parameters

Constant operating temperature
-40 °C to +90 °C, max. 120 °C for 20,000 hours
Rated voltage
0.6/1.0 kV;
Max. short-term operating temperature during a short circuit
+250 °C (max. 5 sec. per strand)
Minimum ambient temperature for permanently installed cables
-40 °C
Cable Installation Temperature
-5 °C to 50 °C
Test voltage at 50 Hz
5,000 V (AC)
Minimum bending radius for static connections
3 x Ø
02

Construction

Insulation
Special halogen-free cross-linked plastic, type EI109, compliant with EN 50264-3-1. Available in black or another color as specified by the customer.

A conductor made of electrolytic tin-plated copper, grade Cu-ETP1, Class 5 stranded wire in accordance with the EN/IEC 60228 standard

03

Properties

Halogen-free according to
IEC 60754-1
Flame resistance tested in accordance with
EN 60332-1-2, EN 60332-3-24, EN 60332-3-25
Smoke emissions during combustion according to
EN/IEC 61034-2
Emissions of toxic gases during combustion according to
EN 50305-9.2
Corrosiveness of Gases During Combustion
EN 50267-2-2

Insulation made of a material resistant to oils, greases, petroleum, ozone, and UV rays

04

Standards

EN 50264-3-1; EN 45545-2

05

Technical Tables

Technical Specifications — (N)HXAF 0.6/1 kV

Technical Specifications — (N)HXAF 0.6/1 kV
Wire cross-sectional area [mm²]Rated insulation thickness [mm]Min. cable diameter [mm]Max. cable diameter [mm]Cable weight [kg/km]
0,50,62,12,49,5
0,750,62,32,612,5
1,00,62,42,814
1,50,72,83,320
2,50,73,23,829
40,73,84,444
60,74,25,062
100,75,15,9102
160,76,17,2161
250,97,89,1248
350,99,010,6326
501,010,612,4477
701,112,514,6666
951,115,015,6868
1201,216,717,31106
06